This product is no longer available and has been superseded by Airstage J-IVS

Technical Specifications

Attribute AJT040LCLAH 12.10kW(C) 13.60kW(H) AJT045LCLAH 14.00kW(C) 16.00kW(H) AJT054LCLAH 15.10kW(C) 16.50kW(H)
Operation Type Reverse Cycle Reverse Cycle Reverse Cycle
Power Source V/Ph/Hz 230 / 1 / 50 230 / 1 / 50 230 / 1 / 50
Capacity Class kW 12.1 14 15.1
EER Cooling kW/kW 3.52 3.31 3.3
COP Heating kW/kW 4.4 4.07 4.01
Total Cooling Seasonal Performance Factor Residential kW (Hot / Average / Cold) 4.462 / 3.802 / 3.798 4.304 / 3.742 / 3.775 4.195 / 3.681 / 3.713
Heating Seasonal Performance Factor Residential kW (Hot / Average / Cold) 4.547 / 3.89 / 3.209 4.387 / 3.335 / 2.764 4.295 / 3.275 / 2.722
Total Cooling Seasonal Performance Factor Commercial kW (Hot / Average / Cold) 4.867 / 4.791 / 5.04 4.681 / 4.654 / 4.919 4.543 / 4.516 / 4.769
Heating Seasonal Performance Factor Commercial kW (Hot / Average / Cold) 4.535 / 3.984 / 3.481 4.379 / 3.793 / 3.098 4.287 / 3.719 / 3.045
Outdoor Sound Pressure dBA (Cooling / Heating) 51 / 54 53 / 55 56 / 56
Outdoor Sound Power dBA 67 69 70
Outdoor Unit Dimensions mm (Height x Width x Depth) 998 x 970 x 370 998 x 970 x 370 998 x 970 x 370
Outdoor Unit Weight kg 86.00 86.00 87.00
Piping Connects mm Ø (Liquid / Gas) 9.52 / 15.88 9.52 / 15.88 9.52 / 15.88
Operation Range Cooling °CDB (Min to Max) -5 to 46 -5 to 46 -5 to 46
Operation Range Heating °CDB (Min to Max) -20 to 21 -20 to 21 -20 to 21
Maximum Connectable Indoor Units 7 8 8
Refrigerant Type R410A R410A R410A
Refrigerant Amount g 4,000 4,000 4,000